PRAESENSA Configure the system | en 93
Bosch Security Systems B.V. Configuration manual 2020-09 | V1.20 | PRAESENSA 1.20
5.7.5 Multifunction power supply
On the Action definitions page of the Multifunction power supply the Control inputs and
control outputs could be defined.
1. Below the Action definitions configuration page, click Multifunction power supply (Mps):
– A screen appears with on overview of the connected Mps(s).
2. Select and click the name of the Mps to be configured.
– A row called Control inputs appears.
– A row called Control outputs appears.
3. Click the + of the Control inputs row:
– A screen appears listed the eight Control Inputs each with the following items:
Item Value Description
Name [#0n] Static text Shows the name of control input which is entered in
section
Multifunction power supply, page 53
Function Static text Shows the name of the function which is selected in
section
Multifunction power supply, page 53
> control
inputs chapter
Operation Selection Select the operation of the function which is selected
in section
Multifunction power supply, page 53
. See
also
Assigning an operation, page 84
.
Call definition Selection Select the call definition which is created in section
Call definitions, page 81
Depending of the selected Function, different parameters could be selected, entered,
added/removed. See
Assigning a function, page 85
for descriptions.
Submit Button Click the Submit button to store the settings: Notice
that you always have to Save the configuration. See
Save configuration, page 102
Configure control inputs
See
Assigning a function, page 85
for functions and
Assigning an operation, page 84
for
operations available for the Mps.
Each of the eight control inputs listed can be individual configured. To do so:
1. Select the operation (and Call definition) from the dropdown list.
2. Select, enter and/or add/remove the parameters belonging to the selected function.
3. Click the Submit button to store the settings. See also
Save configuration, page 102
.
Configure control outputs
1. Click the + of the Control outputs row:
– A screen appears listed the eight control outputs.
2. With the exception of Zone activity, the Name and the function of the control outputs are
static and can only be changed in the section
Multifunction power supply, page 53
.
– Notice that the Zone activity function requires: Priority range selection (Higher and
lower priority) between 0 and 255 and zone selection.
– Notice that if the function text is called Disabled, the control output is disabled in
the section
Multifunction power supply, page 53
.