PRAESENSA Event messages | en 151
Bosch Security Systems B.V. Configuration manual 2020-09 | V1.20 | PRAESENSA 1.20
Originator: MPS
Resolve: This fault recovers when mains recovers.
Recommended action:
Extra information:
18.2.4 Call station
The following fault events can only occur on call stations.
Event: Call station audio path fault
Group: Fault
Occurrence: Logs the audio path fault (microphone audio path fails).
Originator: Microphone that had an audio path fault.
Resolve: When the device disconnects or when it is resolved manually.
Recommended action: Replace/repair call station (microphone).
Event: Extension mismatch
Group: Fault
Occurrence: Logs the mismatch of the number of configured and detected extensions on a
call station.
Originator: Device that had the mismatch.
Resolve: When the error is no longer present or when the device disconnects
Recommended action:
Check the correct number of connected extensions.
Check the configuration.
Check the loop through connections and correct functionality of each extension. Do the
LED-test.
Extra information: Number of configured extensions. Number of detected extensions
Event: PoE supply failure
Group: Fault
Occurrence: Logs the failure of the backup power supply of the call station. Can only occur
when the number of connected PoE inputs is less than the configured expected PoE inputs.
Originator: Device that had the PoE supply fault.
Resolve: When the error is no longer present or when the device disconnects.
Recommended action: Check the PoE output source (MPS), (network) lines and
connections.
18.2.5 Open Interface client
The following general events can only occur on Open Interface clients.
See the PRAESENSA Open Interface manual for all events.
Event: Device connected via Open Interface
Group: General
Occurrence: Logs the connection of an Open Interface client (like a PC Call Station.
Originator: Open Interface client that connected (which includes the user ID used for the
connection).
Recommended action: None.