18.2 Device specific events
Each PRAESENSA network device could generate it's own event messages. The following
sections represent the events per device type.
–
System controller, page 145
–
Amplifier, page 146
–
Multifunction power supply (MPS), page 147
–
Call station, page 151
–
Open Interface client, page 151
18.2.1 System controller
The following general and fault events can occur only on system controllers.
General events
Event: Backup restored
Group: General
Occurrence: Logs the corruption / consistency error in the configuration (default
configuration loaded when occurring at start-up)
Originator: The System Controller and the user that triggered the restore.
Resolve: Immediately after acknowledgement.
Recommended action:
Extra information:
Event: System restarted
Group: General
Occurrence: Logs the start-up of the system controller.
Originator: Device that started.
Fault events
Event: Power supply fault: input A and/or B
Group: Fault
Occurrence: Logs the failure of power supply input A and/or B. Can only occur when
supervision is enabled for input A/B.
Originator: Device which indicate power supply failure on input A/B.
Resolve: When the error is no longer present or when the device disconnects.
Recommended action: Check/replace the powering device, lines and connections.
Event: Message missing
Group: Fault
Occurrence: Logs the mismatch of the configured and detected messages.
Originator: Device which had the mismatch.
Resolve: When the error is no longer present.
Recommended action: Reload/restore the (involved) correct messages.
Extra information: Name(s) of message(s) present in configuration but not on disk.