158 en | Tones PRAESENSA
2020-09 | V1.20 | PRAESENSA 1.20 Configuration manual Bosch Security Systems B.V.
– Alarm_MS_800-970Hz_100%_10x1s.wav
– Sweep 800 Hz - 970 Hz, up in 1 s, 10 repetitions
– Duty cycle 100%, Peak level -1.3 dBFS, RMS level <-9 dBFS
– UK, BS 5839-1 “Fire”
– Alarm_MS_800-970Hz_100%_70x0.14s.wav
– Sweep 800 Hz - 970 Hz, up in 0.14 s, 70 repetitions
– Duty cycle 100%, Peak level -1.3 dBFS, RMS level <-9 dBFS
– UK, BS 5839-1 “Fire”
– Alarm_MS_800-970Hz_25%_3x(0.5+0.5)s+1s.wav
– Sweep 800 Hz - 970 Hz, up in 0.5 s, 0.5 s off, up in 0.5 s, 0.5 s off, up in 0.5 s, 1.5 s
off
– Duty cycle 25%, Peak level -1.3 dBFS, RMS level <-9 dBFS
– ISO 8201
– Alarm_MS_970Hz_25%_3x(0.5+0.5)s+1s.wav
– Intermittent 970 Hz, 0.5 s on, 0.5 s off, 0.5 s on, 0.5 s off, 0.5 s on, 1.5 s off
– Duty cycle 25%, Peak level -1.3 dBFS, RMS level <-9 dBFS
– ISO 8201 “Low tone”
– Alarm_MS_970Hz_20%_8x(0.25+1.00)s.wav
– Intermittent 970 Hz, 0.25 s on, 1 s off, 8 repetitions
– Duty cycle 20%, Peak level -1.3 dBFS, RMS level <-9 dBFS
– “General purpose”
– Alarm_MS_970Hz_50%_5x(1+1)s.wav
– Intermittent 970 Hz, 1 s on, 1 s off, 5 repetitions
– Duty cycle 50%, Peak level -1.3 dBFS, RMS level <-9 dBFS
– UK, BS 5839-1 “Alert”, PFEER “Alert”
– Alarm_MS_970Hz_100%_10s.wav
– Continuous 970 Hz, 10 s
– Duty cycle 100%, Peak level -1.3 dBFS, RMS level <-9 dBFS
– UK, BS 5839-1 “Evacuate”, PFEER “Toxic gas”
– Alarm_MS_970+630Hz_100%_10x(0.5+0.5)s.wav
– Alternating 970 Hz, 0.5 s and 630 Hz, 0.5 s, 10 repetitions
– Duty cycle 100%, Peak level -1.3 dBFS, RMS level <-9 dBFS
– UK, BS 5839-1
– Alarm_MS_1000+2000Hz_100%_10x(0.5+0.5)s.wav
– Alternating 1000 Hz, 0.5 s and 2000 Hz, 0.5 s, 10 repetitions
– Duty cycle 100%, Peak level -1.3 dBFS, RMS level <-9 dBFS
– Singapore
– Alarm_MS_1200-500Hz_100%_10x1s.wav
– Sweep 1200 Hz - 500 Hz, down in 1 s, 10 repetitions
– Duty cycle 100%, Peak level -1.3 dBFS, RMS level <-9 dBFS
– Germany, DIN 33404 Part 3, PFEER “Prepare for evacuation”
– Alarm_MS_1400-1600-1400Hz_100%_8x(1.0+0.5)s.wav
– Sweep 1400 Hz - 1600 Hz, up in 1.0 s, down in 0.5 s, 8 repetitions
– Duty cycle 100%, Peak level -1.3 dBFS, RMS level <-9 dBFS
– France, NFC 48-265
– Alarm_MS_2850Hz_25%_3x(0.5+0.5)s+1s.wav
– Intermittent 2850 Hz, 0.5 s on, 0.5 s off, 0.5 s on, 0.5 s off, 0.5 s on, 1.5 s off
– Duty cycle 25%, Peak level -1.3 dBFS, RMS level <-9 dBFS
– USA, ISO 8201 “High tone”