Rexroth IndraDrive Appendix 13-7
DOK-INDRV*-HMV-*******-PR01-EN-P
HMV01.1E
Power Supply
In case of mains voltages with 3 x AC 380 ... 480 V (±10 %) the power
supply unit can be connected directly to the mains; no other components
are necessary.
Note: For interference suppression we recommend a line filter HFD.
supply unit
HMV01.1E
HMVE_NFD_anschluss.fh7
mains filter
L1
L2
L3
PE
1)
2)
mains choke
3)
1) Like mains wires, but not smaller than 10 mm
2
2) Twist main wires - cable selections according to EN 60 204
3) Whether a mains choke is necessary or not depnds on the
continuous DC bus power (see electrical data).
Fig. 13-6: Direct mains connection via mains filter
Direct mains connection [with
3 x AC 380 ... 480 V (±10 %)]