7-8 Electrical Installation Rexroth IndraDrive
DOK-INDRV*-HMV-*******-PR01-EN-P
HMV01.1R-W0018, -W0045, -W0065
Designation Symbol Unit HMV01.1R-
W0018
HMV01.1R-
W0045
HMV01.1R-
W0065
kind of connection (mode of operation at
the mains)
- - 3-phase
mains input voltage (rated voltage) U
LN
V 380 -10% to 480 +10%
transient overvoltage limit values U
L trans max
V 1200
mains frequency f
LN
Hz 48 to 62
Maximum mains frequency change per
time unit
df
LN
/t Hz/s 2% * f
LN
mains input continuous current (r.m.s.
value)
I
L cont
A 30 70 100
connected mains power with DC bus
choke (at max. DC bus power)
S
LN (L_DC)
kW 18 45 65
power factor (cosϕ)cosϕ
-1
DC bus voltage (range) U
DC
V 750 (controlled)
upper DC bus voltage limit (shutdown
threshold)
U
DC limit (max)
V 900
lower DC bus voltage limit (shutdown
threshold)
U
DC limit (min)
V 0,75 * ¥2 * U
LN
continuous DC bus power (at U
LN
=400V) P
DC cont
kW 18 45 65
continuous DC bus power depending on
mains input voltage
at U
LN
< 400 V: 1% power reduction per 4 V
at U
LN
> 400 V: no power increasing
DC bus peak power
(for max. 0,3 s with a preload of
0,6 x I
LN cont
and 40 °C ambient
temperature)
P
DC peak
kW 45 112 162
braking resistor switch-on threshold U
DC (R_DC On)
V 820
continuous brake power (braking resistor) kW
0,4 0,4 0,4
maximum brake power (braking resistor) kW
36 90 130
brake energy absorption (braking resistor) kWs
80 100 150
DC bus capacity C
DC
µF
705 1880 2820
output voltage U
out eff
V 750 (controlled)
overload capacity
factor / duration
I
out_max1/
I
out_cont1
A factor 2,5
(related to rated power)
power dissipation P
Diss
W 290 680 800
Fig. 7-4: Technical data