7.3 Electrical Data
HMV01.1E-W0030, -W0075, -W0120
Designation Symbol Unit HMV01.1E-W0030 HMV01.1E-W0075 HMV01.1E-W0120
kind of connection (mode of operation at
the mains)
- - 3-phase
mains input voltage (rated voltage) U
LN
V 380 -10% to 480 +10%
transient overvoltage limit values U
L trans max
V 1200
mains frequency f
LN
Hz 48 to 62
Maximum mains frequency change per
time unit
df
LN
/t Hz/s 2% * f
LN
mains input continuous current (r.m.s.
value)
I
LN cont
A 50 125 200
connected mains power without DC bus
choke (at max. DC bus power)
1)
S
LN
kW 18 45 72
connected mains power with DC bus
choke (at max. DC bus power)
S
LN (L_DC)
kW 30 75 120
power factor (cosϕ)cosϕ
-1
DC bus voltage (range) U
DC
V 435 to 710
upper DC bus voltage limit (shutdown
threshold)
2)
U
DC limit (max)
V 900
lower DC bus voltage limit (shutdown
threshold)
3)
U
DC limit (min)
V 0,75 *
¥
2 * U
LN
continuous DC bus power (at U
LN
=400V)
with choke
4)
P
DC cont
kW 30 75 120
continuous DC bus power (at U
LN
=400V)
without choke
P
DC cont
kW
18 45 72
continuous DC bus power depending on
mains input voltage
at U
LN
< 400 V: 1% power reduction per 4 V
at U
LN
> 400 V: 1% power increasing per 4 V
peak DC bus power
(for max. 0,3 s with a preload of
0,6 x I
LN cont
and 40 °C ambient
temperature)
P
DC peak
kW
45 112 180
braking resistor switch-on threshold U
DC (R_DC On)
V constant 820V or
variable 80V +
¥
2 * U
LN
continuous brake power kW 1,5 2 2,5
maximum brake power kW 36 90 130
brake energy absorption kWs 100 250 500
DC bus capacity C
DC
µF
1410 3760 5640
overload capacity
factor / duration
I
out_max1/
I
out_cont1
A factor 2,5
(related to rated power without DC bus choke)
power dissipation
P
Diss
W 150 340 500
1) These data refer to a supply impedance of 40 µH.
2) When the upper DC bus voltage limit has been reached, the supply unit does
not switch off. The display shows a warning message. The output stages of
the drive controllers are locked.
3) When the lower DC bus voltage limit has been reached, the supply unit does
not switch off. The display shows a warning message. At an undervoltage of
0,75 * U
LN
the supply unit switches off.
4) Inductance of the choke:
HMV01.1E-W0030: 400 µH
HMV01.1E-W0075: 200 µH
HMV01.1E-W0120: 100 µH
Fig. 7-3: Technical data