7-30 Electrical Installation Rexroth IndraDrive
DOK-INDRV*-HMV-*******-PR01-EN-P
X14, Mains Voltage Synchronization
The X14 interface is only available for regenerative supply units
(HMV01.1R). It is used to connect the mains voltage synchronization.
hmv_X14
3
2
1
Fig. 7-36: X14
Type Number of poles Type of design
LE 7,62 M PC 4,0 / 3G 3 Connector on device
Fig. 7-37: Design
Cross section
single-wire
[mm²]
Cross section
multiwire
[mm²]
Cross section
in AWG
Gauge No.
1,5 - 4 1,5 - 4 16 - 12
Fig. 7-38: Connection cross section
Pin no. Description Level Notes
3 mains connection phase L3 before choke max. 900V current load max. 5A
2 mains connection phase L2 before choke max. 900V current load max. 5A
1 mains connection phase L1 before choke max. 900V current load max. 5A
Fig. 7-39: Connection X14
Description
Graphic Representation
Design
Connection cross section
Connection