Rexroth IndraDrive Appendix 13-9
DOK-INDRV*-HMV-*******-PR01-EN-P
HMV01.1R
Power Supply
As the power part of the HMV01.1R power supply units consists of a
clocked 3-phase IGBT bridge, a mains choke KDxx will always be needed
for the mains connection. In addition, a so-called combining filter HFD will
be required.
X3
K1
Supply unit
HMV01.1R
power
supply
L2
L1
L3
L2
L1
L3
=
~
Q1
U1
V1
W1
U2
V2
W2
PE
L1.1 L2.1 L3.1
to the central
ground connection
HFD
combining filter
3 x AC 380 - 480 V
50 - 60 Hz
KDxx
mains choke
drive
controller
twisted
HMVR_Netzanschluss.fh7
mains input
L+
L-
+24V
0V
twisted
to the central
ground connection
X14
1
2
3
F2
L1 L2 L3
Fig. 13-8: Mains connection via mains choke and combining filter
Basically, the HFD combining filters to be provided for the mains
connection of the power supply units have two tasks:
• to suppress the current leakages from parasitic capacities of the
construction (motor cable, winding capacities) and
Mains connection with
3 x AC 380 ... 480 V (±10 %)