6 Mechanical Mounting
6.1 Mounting Conditions
Ambient and Operating Conditions
Note: The supply units and their additional components are designed
to be built into control cabinets.
Note: The user must check that the ambient conditions, and in
particular the temperature of the control cabinet, are complied
with by calculating the heat levels in the control cabinet.
Designation Information
Ambient temperature 0 to +40 °C
Ambient temperature with derating 2% per °C to +55 °C
Temperature in storage see chapter 5 "Transport and Storage"
Temperature during transportation see chapter 5 "Transport and Storage"
Mounting altitude at rating 1000 m above sea level
Mounting altitude with derating* Up to 2000 m 2.0% per 100 m from 1000 m
From 2000 m: see characteristic in Fig. 6-3
Maximum mounting altitude* 4000 m
(upper temperature limit falls to 40 °C instead of 55 °C)
Relative humidity
(operation)
5% to 95%
Cl.3K5 with reservation, as not 5 °C
Absolute humidity 1 to 29 g/m
3
Climatic class Cl.3K5
Contamination level Contamination level 2 in accordance with EN50178
Vibration sinus in operation according to
EN 60068-2-6
Amplitude and frequency: 0,15 mm (peak-peak)
at 10 ... 57 Hz
Acceleration and frequency: 1 g at 57 ... 150 Hz
Tolerance: ±15 %
Vibration distortion (Random) in
operation according to IEC 68-2-36
Frequency: 20 ... 150 Hz
Spectral acceleration density amplitude: 0,005 g
2
/Hz
Tolerance: ± 3 dB
Virtual value (r.m.s.) of the total acceleration: 1,0 g
* For mounting altitudes of more than 2000 m, an overvoltage limiter
for transient overvoltage 1.2/50 µs must be installed in the
installation or building in order to limit the voltage to 1.0 kV between
the outer conductors and to 2.5 kV between conductor-ground.
Fig. 6-1: Ambient and operating conditions