Rexroth IndraDrive Mechanical Mounting 6-3
DOK-INDRV*-HMV-*******-PR01-EN-P
Duty Capacity
Where conditions differ, the following performance data diminish in
accordance with the diagrams (see “Fig. 6-2: Duty capacity at higher
ambient temperature” and “Fig. 6-3: Duty capacity at higher mounting
altitude”):
• Permitted DC bus continuous output
• Continuous output of the braking resistor
• Continuous current
If differing ambient temperatures and higher mounting altitudes occur
simultaneously, both duty factors must be multiplied. The mounting
altitude must be taken into account just once, differing ambient
temperatures must be considered separately for the motor and drive
controller.
DG0006F1.FH7
Ambient temperature in °C
0,7
1
40 45 50 55
5
Degree of utilization at higher
ambient temperatures
Load factor
Fig. 6-2: Duty capacity at higher ambient temperature
DG0007F1.FH7
1000 2000
0,8
1
0
3000 4000
0,6
0,4
0,2
Degree of utilization at higher installation altitudes
Load factor
Installation altitude above sea level in meters
Fig. 6-3: Duty capacity at higher mounting altitude