6-6 Mechanical Mounting Rexroth IndraDrive
DOK-INDRV*-HMV-*******-PR01-EN-P
Control Cabinet with Multiple Line Structure
Note: Particular attention should be paid to the maximum
permissible air intake temperature of components when they
are arranged in multiple lines in the control cabinet. Where
necessary, cooling air guides are to be allowed for with
ventilators specially inserted for this purpose.
For
example: air
baffle
Additional
fan
Discharge direction of the
warmed air in the flow-off area
Discharge direction of the
warmed air in the flow-off area
Entry area of the cooling air
for the upper device line
Entry area of the cooling air
for the lower device line
Exhaust air
from the air
conditioner
Supply air
from the air
conditioner
Fig. 6-8: Example of arrangement for multiple line structure with components