Commissioning
Logamatic EMS RC35 user interface - Subject to technical modifications.20
5
5.3 Quick commissioning (Quick operation menu)
B Press to open the quick operation menu.
SHORTCUT Menu item Input range
Factory
setting Other information
BASIC SETUP Which language should
be used?
American,
French,
Spanish
American
LOW LOSS
HEADER
Did you install a low
loss header module?
yes, no no In connection with
MCM10 the setting is
set automatically to
“yes”; the screen
disappears.
UNMIXED HZ Is heating zone 1
installed (unmixed
heating zone)?
yes, no yes
# OF MIX
VALVES
How many mixed
heating zones are
installed?
0 to 3 0 Set the address on the
dial on the MM10 mixing
module
(factory setting: HZ2).
HEATING
ZONE 1
(and other heating
zones)
Which user interface is
assigned to heating
zone 1?
RC20, RC35
none
RC35 To assign user interface
to heating zone
(Æ page 32).
General heating zone
data (Æ page 28).
Set any other heating
zones in the same way
as for heating zone 1.
How should heating
zone 1 be controlled?
outdoor reset,
room reset
outdoor
reset
Which heating system
does heating zone 1
have?
panel radiator,
convector,
floor
panel
radiator
Heating characteristic
curve (Æ page 33)
Tab. 8 Quick operation menu navigator
SERVICE MENU
B
quick operation
settings
diagnosis
servicing