EasyManua.ls Logo

Buderus Logamatic EMS - Reduction Modes (Night Setback)

Buderus Logamatic EMS
60 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Entering system settings (Service menu – Settings)
Logamatic EMS RC35 user interface - Subject to technical modifications.34
6
Fig. 6 Setting the characteristic heating curve
Left: setting the gradient by means of standard temperature and design day temperature
Right: parallel shift possible by means of offset or target room temperature
T
minA
Minimum outdoor temperature
T
A
Standard temperature (i.e. the design temperature – the supply temperature to be reached at design day
temperature)
1 Setting: design temperature 167 °F (75 °C), minimum outdoor temperature 14 °F (–10 °C) (base curve)
2 Adjustment: Design temperature 167 °F (75 °C), minimum outdoor temperature 4 °F (–20 °C)
3 Adjustment: Design temperature 122 °F (50 °C), minimum outdoor temperature 14 °F (–10 °C)
4 Setting: minimum supply temperature 95 °F (35 °C)
5 Setting: design temperature 167 °F (75 °C), minimum outdoor temperature 14 °F (–10 °C) (base curve)
6 Parallel shifting of base curve by changing the offset +6 °F (+3 °C) or by increasing the target room
temperature
7 Parallel shifting of base curve by changing the offset –6 °F (–3 °C) or by reducing the target room
temperature
6.3.4 Reduction modes (night setback)
There are a number of different reduction modes available, which allow night setback to be adjusted
to suit the differing needs of the user:
setback mode: The rooms are maintained at a reasonable temperature by constant heating
operation (the heating zone pump runs constantly). A target room temperature for nighttime can
be set. This must be at least 2 °F (1 °C) lower than the daytime target room temperature. The
heating characteristics will be calculated in accordance with this setting.This setting is
recommended for radiant floor heating.

Related product manuals