Entering system settings (Service menu – Settings)
Logamatic EMS RC35 user interface - Subject to technical modifications.26
6
Example:
Fig. 5 This greatly simplified example shows how the delayed response to outdoor temperature
follows the outdoor temperature, but does not reach its extreme values.
1 Current outdoor temperature
2 Adjusted outdoor temperature
6.1.2 Minimum outdoor temperature
The “minimum outdoor temperature” is the mean of all the coldest outdoor temperatures of recent
years, and helps to determine the heating characteristics. The value can be taken from the heat
requirement calculation that should be done for every building, or from the climatic zone chart of your
region.
With the factory setting, changes in the outdoor temperature will affect the calculations
for outdoor-temperature-based control after a delay of no more than three hours
(30 x 6 minutes = 180 minutes).
B To monitor the calculated, delayed response to outdoor temperature and the
currently recorded outdoor temperature:
open the menu Diagnosis\Monitor\boiler/burner.