Entering system settings (Service menu – Settings)
Logamatic EMS RC35 user interface - Subject to technical modifications.40
6
6.6 RC35 calibration
B Turn the dial counter-clockwise until RC35 calibration is
selected (marked with).
B Press to select RC35 calibration.
The SETTINGS\CALIB. RC35 menu is opened.
Calibration of the displayed room temperature
If there is a separate thermometer near the controls, it may show a different room temperature to that
shown on the RC35. This function can be used to adjust the RC35 to match the thermometer
(i.e. “calibrate”).
Before calibrating the room temperature, consider the following:
• Is the thermometer more accurate than the RC35?
• Is the thermometer located close to the unit so that they are both subject to the same heat
influences (e.g. sunlight, fireplace)?
Example: if the thermometer is showing a temperature 2 °F (1 °C) higher than the controls, enter
“+2 °F (+1 °C)” as the calibration value.
Menu item Input range Factory setting Other information
Calibration of the room
temperature
–9.0 °F – +9.0 °F
(–5.0 °C – +5.0 °C)
0.0 °F (0.0 °C)
Tab. 16 Navigator for Service menu SETTINGS\CALIB. RC35
Other thermometers may show temperature changes more slowly or more quickly than
the RC35.
B Never calibrate the controls when your heating system is in the process of cooling
down or heating up, but only in steady state conditions.
domestic hot water
SERVICE\SETTINGS
B
heating zone 1
solar data
RC35 calibration