Entering system settings (Service menu – Settings)
6
RC35 programming unit - Technical specifications are subject to change without prior notice.
28
At what outside temp.
should reduction be
interrupted?
OFF
OFF, -30°C to +10°C
Setback in accordance with EN
12831 standard (see page 34).
Should domestic hot water
priority be activated?
Yes, No
Mixer1)
Is a mixer installed? Yes, No Can only be set for heating circuits
2 and up.
1)
What running time does
the mixer have?
120 seconds
10 to 600 seconds
1)
What increase should be
used for the boiler?
5K
0 to 40K
1)
Drying floor screed1)
Should a drying cycle be
carried out?
Yes No Can only be set if floor heating has
been entered as the heating sys-
tem. DHW heating is not enabled
while screed is drying.
1)
Every how many days
should the flow temp. be
raised?
Every day, every 2nd day to
every 5th day
1)
By how many degrees
Kelvin should the flow
temp. be raised each
time?
5K
0 to 10K
1)
What is the desired max-
imum flow temperature?
45°C
25°C to 60°C
1)
For how many days
should maximum flow
temp. be maintained?
4 days
0 to 20 days
1)
Every how many days
should the flow temp. be
reduced?
Direct normal operation,
every day, every 2nd day to
every 5th day
1)
Menu item
Input range
Factory setting in bold Other information
Table 11 Navigator for Service menu SETTINGS \ HTG. CIRC. 1