22
ADJUSTMENT
FUNCTIONALITY SWITCHES
MN
L2T
L T
0
17
26
10 11 E1 1 2 3P 5 7 2 C1 C3 C7 C8
TS
+E
-
FC FA
F
L NE FUSE
230V=1 6A F
120V=3 15A F
MOTOR FUSE
BX243=8A F
BX246=10A F
ACCESSORIES
FUSE
1 6A F
C BOARD
FUSE
1A F
+
RUN S
- +
SLOW S
- +
RUN V
- +
SLOW V
-
+
A C T
-
+
PAR OP
-
ZN5U5
ZN5
CONTROL BOARD
PWR
1
C1
C3
C7
C8
ON
2
1 345678910
PROG
MN
L2T
L1T
LN
0
17
26
10 11 E1 1 2 3P 5 7 2 C1 C3 C7 C8
TS
+E
-
FC FA
F
/.
ON
OFF
Default Setting
FUNCTIONALITY SWITCHES
SWITCH SETTING FUNCTION
1 ON Automatic Closing - The automatic close timer (ACT) is activated when the gate is open. The pre-set time is adjustable, depending of the
activation of any safety devices, and does not activate after a total safety “stop” or during a blackout.
2 ON “Open-stop-close-stop” function with [2-7] command button and remote control (if a radio frequency card is installed).
OFF “Open-close” function with [2-7] command button and remote control (if a radio frequency card is installed).
3 ON “Open only” function with [2-7] command button and remote control (if a radio frequency card is installed).
4 OFF Not used. Leave OFF.
5 OFF With BX-243 motor.
ON With BX-246 motor.
6 ON Maintained action - The gate activates with constant pressure from command button (one 2-3P opening button, and one 2-7 closing button).
7 ON Functioning of the photoelectric sensors’ safety test - Allows the card to check the efficiency of any safety devices (i.e. photoelectric sensors)
after every opening or closing command.
8 OFF Total stop - This function stops the gate and then excludes any automatic closing cycle; to set in motion again, use either the keypad or
transmitter. Insert the safety device in [1-2]; If unused, set DIP switch to ON.
9 OFF OPENING DURING CLOSING - If the photoelectric sensors detect an obstacle while the gate is closing, the gate reverses until fully opened;
connect the safety device to terminals [2-C1]; if unused, set DIP switch to ON.
10 OFF PARTIAL STOP - Gate stops when an obstacle is detected by the safety device; once the obstacle is removed, the gate remains still or closes
if automatic closing is activated. Connect the safety device to terminal [2-C3]; if unused, set the DIP switch to ON.