Emotron VS Series Quick Start Guide
- 67 -
Unit’s place: External equipment
fault (Err13)
0: Fault reported and coast to
stop
1: Stop according to the stop
mode
2: Fault reported but continue to
run
Ten's place: EEPROM read/write
fault (Err15)
(Same as unit's place)
Hundred's place: Communication
overtime error (Err18)
(Same as unit's place)
Thousand's place: PID feedback
loss (Err19)
(Same as unit's place)
Ten thousand's place: Continuous
running time reached (Err20) (Same
as unit's place)
Unit's place: Module temperature
detection disconnection(Err24)
0: Fault reported and coast to
stop
1: Stop according to the stop
mode
2: Fault reported but continue to
run
3: Fault protection disabled
Ten's place: Load becoming 0
(Err25) (Same as unit's place)
Frequency selection for
continuing to run upon fault
0: Current running frequency
4: Backup frequency upon
abnormality
Backup frequency upon
abnormality
Motor overload protection
time
Unit's place: detection option:
0: Always detect
1: Detect at constant speed only
Ten's place: compared object
0: Rated current of motor
1: Rated current of drive
Hundred’s place: Fault reported
0:No fault reported
1:Fault reported
Thousand’s place: whether to
decelerate or not when overload
alarm
0: No deceleration
1: Deceleration
Ten thousand's place: given mode
for overload threshold