Technical data CHLORIDE ACTIVE
GB - 40 V02OCT/01 945040.066
UPS model
ACTIVE
700
ACTIVE
1000
ACTIVE
2000
ACTIVE
3000
Electrical safety EN 50091-1; EN 60950
Radio interference level EN 50091-2, Class B
Emitted interference EN 50081-1
Interference immunity
EN 50082-1
IEC 801-2,Level 4 / IEC 801-3,Level 3
IEC 801-4,Level 4 / IEC 801-5,Level 3
Mains pollution EN 61000-3-2, EN 61000-3-3
Efficiency > 83 % 90 %
Degree of protection IP20
Cooling Fan
Noise level
in dB(A), typical
Mains operation, <39 <39 <45 <45
battery operation <40 <40 <46 <46
Perm. ambient temperature during operation
10°C to + 40°C
recommended +15°C to + 32°C
Perm. ambient temperature during storage -15°C to + 40°C
Perm. rel. humidity during operation 20% to 90%, no condensation perm.
Installation altitude
max. 3000m, from 1500m max.
Ambient temperature = 35°C
Table 8: General data (ACTIVE 700 to ACTIVE 3000)
UPS model
ACTIVE
700
ACTIVE
1000
ACTIVE
2000
ACTIVE
3000
UPS
Weight / kg 11,5 14 33 33
Dimensions / mm
Width
Height
Depth
145
225
405
200
350
405
Battery extension
Model
BPACTIVE
1000
BPACTIVE
3000
BPACTIVE
3000
Weight / kg 19 48 48
Dimensions / mm
Width
Height
Depth
145
225
405
200
350
470
Table 9: Mechanical data (ACTIVE 700 to ACTIVE 3000)

Table of Contents