CHLORIDE ACTIVE Technical data
945040.066 V02OCT/01 GB - 39
G
B
Technical data
Technical data for the models ACTIVE 700 to
ACTIVE 3000
UPS model
ACTIVE
700
ACTIVE
1000
ACTIVE
2000
ACTIVE
3000
Power
700 VA 1 kVA 2 kVA 3 kVA
Input
Voltage 1 N AC 220/230/240V
Voltage range 160 V to 276 V
Frequency 50/60Hz ± 5%, automat. frequency detection
Power factor (lambda) 0,95
Battery
Integrated battery
Model Lead, maintenance free
Voltage/V 24 36 96 96
Autonomy time,
half-load/full-load/min
12/6 15/7 24/10 14/6
Autonomy time, 1 battery exten-
sion half-load/full-load/min
56/28 84/37 52/25
Autonomy time, 2 battery exten-
sions half-load/full-load/min
105/48 157/69 97/43
Output
Voltage 1 N AC 220,230,240 V
Voltage tolerance ± 3%
Frequency line-clocked see Input frequency
Frequency self-clocked 50/60Hz ± 0.5%
Harmonic distortion
(linear/non-linear load)
max. 4% / max. 8%
Perm. crest factor 3
Overload capacity
130% for 1.5 sec, 110% for 10 sec
Output is short-circuit proof
Table 7: Electrical data (ACTIVE 700 to ACTIVE 3000)