5.1.3.- DETECTION OF INCORRECT DIRECTION OF ROTATION
The device has a system for detecting the incorrect direction of rotation of the voltages. In other words,
if each of the voltages has been correctly connected to the appropriate terminal, L1 to terminal UL1, L2
to terminal UL2 and L3 to terminal UL3.
If there is an error in the direction of rotation, the icons L1, L2 and L3 flash on the display.
The device has a RS-485 communications parameter, which indicates whether an incorrect direction of
rotation has been detected (“7.3.7. DETECTION OF INCORRECT DIRECTION OF ROTATION.”)
Note: The detection of the direction of rotation is only enabled for measurement systems: Three-phase
network measurement (4-3Ph, 3-3Ph y 3-ArOn) and two-phase network measurement with 3-wire
connection (3-2Ph).
5.2.- e
3
PROFILE
This profile is identified with the symbol at the top of the screen.
The installation's consumed and generated energy are displayed on the e
3
profile of the device.
The installation status is also displayed:
Installation is consuming energy.
Installation is generating energy.
A long keystroke, ≥ 3 sec, of key will display the generation values. The generation values are
identified with the negative sign on the screen, which appears in front of each parameter.
A long keystroke, ≥ 3 sec, of key will display the consumption values.
Use keys and to browse the different screens.
Active Energy Tariff 1
Active Energy Tariff 2
Active Energy Tariff 3
Total Active Energy, ∑
Consumption and generation values only available for the 4 quad-
rant option.
Apparent Energy Tariff 1
Apparent Energy Tariff 2
Apparent Energy Tariff 3
Total Apparent Energy, ∑
Consumption and generation values only available for the 4 quad-
rant option.
33
Instruction Manual
CVM-C11