Press key for 3 seconds to edit the value. The icon appears at the top of the screen.
To enter or modify the value, press the key repeatedly, increasing the value of the flashing digit.
When the desired value is shown on the screen, move onto the next digit by pressing the key to
modify the other values.
The programmed value will be deleted if the entered value is higher than the maximum programming
value.
To validate the data, press for 3 seconds and the icon will disappear from the display.
Configuration values
Table 52:Configuration values: Kilowatts per pulse.
Energy CO
2
Emissions Cost No. of hours
Minimum value 000.000 kWh 00000.0 kWh 00000.0 kWh 00000.0 kWh
Maximum value 999.999 kWh 99999.9 kWh 99999.9 kWh 99999.9 kWh
Example: To program 500 Wh per pulse: 000.500
To program 1.5 kWh per pulse: 001.500
Press key to access the next programming step.
6.27.2.- PULSE WIDTH
The width of the pulse is selected on this screen in ms.
Press key for 3 seconds to edit the value. The icon appears at the top of the screen.
To enter or modify the value, press the key repeatedly, increasing the value of the flashing digit.
When the desired value is shown on the screen, move onto the next digit by pressing the key to
modify the other values.
64
CVM-C11
Instruction Manual