In the case of some parameters (Table 43), you can modify the position of the decimal point. To do so,
press key after modifying the last digit and the decimal point will start flashing.
Press key repeatedly to modify the position of the decimal point.
When the decimal point is in the desired position, press the key to end the programming, pressing
now the key we can set a positive or negative value.
Note: Pay special attention when programming the Generation Power (displayed with negative values).
Example: If you wish to enter a generation power alarm with limits between 2 kW and 1 kW, program
the following as the maximum value : - 1 kW and the following as the minimum value : - 2 kW.
To validate the data, press for 3 seconds and the icon will disappear from the display.
Press key to access the next programming step.
6.25.3.- CONNECTION TIME DELAY
The alarm connection delay is programmed on this screen in seconds.
Press key for 3 seconds to edit the value. The icon appears at the top of the screen.
To enter or modify the value, press the key repeatedly, increasing the value of the flashing digit.
When the desired value is shown on the screen, move onto the next digit by pressing the key to
modify the other values.
To validate the data, press for 3 seconds and the icon will disappear from the display.
Configuration values
Table 46:Configuration values: Connection time delay.
Connection time delay
Minimum value 0 seconds
Maximum value 9999 seconds
Press key to access the next programming step.