Press key repeatedly to modify the position of the decimal point.
When the decimal point is in the desired position, press the key to end the programming, pressing
now the key we can set a positive or negative value.
Note: Pay special attention when programming the Generation Power (displayed with negative values).
Example: If you wish to enter a generation power alarm with limits between 2 kW and 1 kW, program
the following as the maximum value : - 1 kW and the following as the minimum value : - 2 kW.
To validate the data, press for 3 seconds and the icon will disappear from the display.
Configuration values
Table 45: Decimal point and units of the alarm parameters.
Types of parameters Units Decimal point
Voltage
2000 kV
200.0 kV
20.00 kV
2.000 kV
Programmable
Current A Programmable
Frequency
Hz
Fixed
Power kW Programmable
Power factor PF Fixed
Cosine φ
φ
Fixed
Maximum current demand A Programmable
Maximum power demand
kW Programmable
THD % Fixed
Press key to access the next programming step.
6.25.2.- MINIMUM VALUE
On this screen, the value below which the alarm is activated is programmed.
Press key for 3 seconds to edit the value. The icon appears at the top of the screen.
To enter or modify the value, press the key repeatedly, increasing the value of the flashing digit.
When the desired value is shown on the screen, move onto the next digit by pressing the key to
modify the other values.
58
CVM-C11
Instruction Manual