When the desired value is shown on the screen, move onto the next digit by pressing the key to
modify the other values.
To validate the data, press for 3 seconds and the icon will disappear from the display.
The programmed value will be deleted if the entered value is higher than the maximum programming
value.
Configuration values
Table 19:Configuration values: Primary current.
Primary current
Minimum value 1
Maximum value 10000
Voltage ratio x Current ratio < 600000
Note: The ratio is the relation between the primary and the secondary.
Press key to access the next programming step.
6.4.- SECONDARY CURRENT
On this screen the current transformer secondary is selected.
Press key for 3 seconds to edit the value. The icon appears at the top of the screen.
The key jumps between the possible options.
To validate the data, press for 3 seconds and the icon will disappear from the display.
Configuration values
Table 20:Configuration values: Secondary current.
Secondary current
Possible values
1 A
5 A
Press key to access the next programming step.
40
CVM-C11
Instruction Manual