Table 43 (Continuation): Parameter codes used to program the outputs.
Parameter Phase Code Phase Code Phase Code Phase Code
Apparent Power Maximum
Demand
- - - - - - III 43
Inductive Reactive Power
Maximum Demand
- - - - - - III 132
Capacitive Reactive Power
Maximum Demand
- - - - - - III 133
In addition, there are some parameters (Table 44) that refer to the three phases at the same time (OR
function). If you have selected one of these variables, the alarm will be activated when any of the three
phases meets the programmed conditions.
Table 44: Multiple parameter codes for alarm programming.
Types of parameters Code
Phase-Neutral Voltage 200
Current 201
Active power 202
Inductive Reactive Power 203
Capacitive Reactive Power 204
Power factor 205
Phase-Phase Voltage 206
% THD V 207
% THD A 208
Apparent Power 209
Press key to access the next programming step.
6.25.1.- MAXIMUM VALUE
On this screen, the value above which the alarm is activated is programmed.
Press key for 3 seconds to edit the value. The icon appears at the top of the screen.
To enter or modify the value, press the key repeatedly, increasing the value of the flashing digit.
When the desired value is shown on the screen, move onto the next digit by pressing the key to
modify the other values.
In the case of some parameters (Table 45), you can modify the position of the decimal point. To do so,
press key after modifying the last digit and the decimal point will start flashing.