EasyManua.ls Logo

Circutor RGU-100A - WGC Specifications

Circutor RGU-100A
52 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
42
RGU-10A , RGU-100A
Instruction Manual
9.2 - WGC
Measurement circuit
Type Passant
Network frequency 45... 60 Hz
Assigned transformation ratio (Kn) 30 / 0.06 A
Differential Current measurement circuit
Scale range Scale found Display resolution
30 mA 75 mA ± 1 mA
300 mA 750 mA ± 1 mA
3 A 7.5 A ± 0.1 A
30 A 75 A ± 0.1 A
Model Nominal current (In) Imax/In
(2)
WGC 20 < 63 A 240 A / 30 mA
WGC 25 < 63 A 240 A / 30 mA
WGC 30 63... 80 A 480 A / 30 mA
WGC 35 63... 80 A 480 A / 30 mA
WGC 55 80... 160 A 500 A / 30 mA
WGC 80 160... 250 A 900 A / 300 mA
WGC 110 250... 400 A 1500 A / 500 mA
WGC 140 400... 600 A 2000 A / 1000 mA
WGC 180 600... 800 A 3600 A / 1000 mA
WGC 220x105 1000... 1250 A 7500 A / 3000 mA
WGC 350x150 1500... 2000 A 10000 A / 3000 mA
WGC 500x200 2500... 4000 A 10000 A / 3000 mA
(2)
Imax: Maximum transient current (peaks)
In: Adjusted tripping current at the earth leakage relay.
Electrical insulation
Maximum operating voltage 0.72 kV
Isolation voltage 3 kV
Installation category CAT III
Environmental features
Operating temperature -10 ºC ... +60 ºC
Storage temperature -20 ºC ... +70 ºC
Relative humidity (non-condensing) 5 ... 95%
Maximum altitude 2000 m
Protection rating Case: IP40 - Terminals: IP20
Mechanical features
Primary connection
Model Windows Conductors section (3F+N)
WGC 20 20 4 x 6 mm
2
WGC 25 25 4 x 6 mm
2
WGC 30 30 4 x 10 mm
2
WGC 35 35 4 x 25 mm
2
WGC 55 55 4 x 70 mm
2

Table of Contents