CB FALCON
750-265 112
194 Invalid ignite failure response setting 1. Return to Configuration mode and recheck selected
parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
L
195 Invalid ignite failure retries setting L
196 Invalid ignition source setting L
197 Invalid interlock open response setting L
198 Invalid interlock start check setting L
199 Invalid LCI enable setting L
200 Invalid lightoff rate setting L
201 Invalid lightoff rate proving setting L
202 Invalid Main Flame Establishing Period time L
203 Invalid MFEP flame failure response setting L
204 Invalid NTC sensor type setting L
205 Invalid Outlet high limit response setting L
206 Invalid Pilot Flame Establishing Period
setting
L
207 Invalid PII enable setting L
208 Invalid pilot test hold setting L
209 Invalid Pilot type setting L
210 Invalid Postpurge time setting L
211 Invalid Power up with lockout setting L
212 Invalid Preignition time setting L
213 Invalid Prepurge rate setting L
214 Invalid Prepurge time setting L
215 Invalid Purge rate proving setting L
216 Invalid Run flame failure response setting L
217 Invalid Run stabilization time setting L
218 Invalid Stack limit enable setting L
219 Invalid Stack limit response setting L
220 Unconfigured Delta T limit setpoint setting L
221 Unconfigured DHW high limit setpoint
setting
L
222 Unconfigured Outlet high limit setpoint
setting
L
223 Unconfigured Stack limit setpoint setting L
224 Invalid DHW demand source setting L
225 Invalid Flame threshold setting L
226 Invalid Outlet high limit setpoint setting L
227 Invalid DHW high limit setpoint setting L
228 Invalid Stack limit setpoint setting L
229 Invalid Modulation output setting L
230 Invalid CH demand source setting L
231 Invalid Delta T limit delay setting L
232 Invalid Pressure sensor type setting L
233 Invalid IAS closed response setting L
234 Invalid Outlet high limit enable setting L
235 Invalid Outlet connector type setting L
236 Invalid Inlet connector type setting L
237 Invalid DHW connector type setting L
238 Invalid Stack connector type setting L
Table 49. Falcon Lockout and Hold Codes. (Continued)
Code Description Recommended Troubleshooting of Lockout Codes NOTE