Section 4 — CFC Commissioning
Part No. 750-263 4-9
Modulation Configuration CH max. mod. rate Service 2000 5000 6000 RPM 0193
Modulation Configuration DHW max. mod. rate Service 2000 5000 6000 RPM 0194
Modulation Configuration Minimum mod. rate Service 900 1100 3000 RPM 0195
Modulation Configuration CH forced rate Service 1000 2000 6500 RPM 0199
Modulation Configuration CH forced rate time Service 0 0 14400 seconds 0200
Modulation Configuration DHW forced rate Service 1000 2000 6500 RPM 0201
Modulation Configuration DHW forced rate time Service 0 0 14400 seconds 0202
Modulation Configuration CH slow start enable Service Enabled 0477
Modulation Configuration DHW slow start enable Service Disabled 0478
Modulation Configuration Slow start ramp Service 100 500 5000
RPM/
minute 0479
Modulation Configuration Slow start setpoint Service 0 20 180
deg (below
SP) 0480
Modulation Configuration Analog output hysteresis Hidden 0 5 400
steps
(5=0.1 mA) 0206
Modulation Configuration Analog input hysteresis Service 0 2 200
steps
(1=0.1mA) 0543
Modulation Configuration Firing rate control User Auto 0204
Modulation Configuration Manual firing rate User 900 2000 6500 RPM 0205
Pump Configuration CH pump output Service No assignment 0272
Pump Configuration CH pump control Service Auto 0273
Pump Configuration CH pump overrun time Service 0 300 28800 seconds 0274
Pump Configuration
CH pump frost protection
overrun time Service 0 3600 28800 seconds 0275
Pump Configuration DHW pump output Service Pump B 0276
Pump Configuration DHW pump control Service Auto 0277
Pump Configuration DHW pump overrun time Service 0 60 28800 seconds 0278
Pump Configuration
DHW pump frost protection
overrun time Service 0 3600 28800 seconds 0279
Pump Configuration DHW pump start delay Service 0 0 28800 seconds 0280
Pump Configuration Boiler pump output Service No assignment 0281
Pump Configuration Boiler pump control Service Auto 0282
Pump Configuration Boiler pump overrun time Service 0 300 28800 seconds 0283
Pump Configuration Auxiliary 1 pump output Service Pump A 0284
Pump Configuration Auxiliary 1 pump control Service Auto 0285
Pump Configuration Auxiliary 1 pump on when Service Local burner demand 0286
Pump Configuration System pump output Service No assignment 0287
Pump Configuration System pump control Service Auto 0288
Pump Configuration System pump overrun time Service 0 900 28800 seconds 0289
Pump Configuration Pump exercise interval Service 0 0 28800 seconds 0290
Pump Configuration Pump exercise time Service 0 0 28800 seconds 0291
Pump Configuration CH pump start delay Service 0 0 28800 seconds 0292
Pump Configuration Boiler pump start delay Service 0 0 28800 seconds 0293
Pump Configuration System pump start delay Service 0 0 28800 seconds 0294
Pump Configuration Auxiliary 1 pump start delay Service 0 0 28800 seconds 0295
Pump Configuration CH pump options 1 Service 0XE327 0296
Pump Configuration CH pump options 2 Service 0xC04E 0297
Pump Configuration DHW pump options 1 Service 0xE04A 0298
Pump Configuration DHW pump options 2 Service 0xC016 0299
Pump Configuration Boiler pump options 1 Service 0xE30F 0300
Table 4-1 CFC default parameter settings
Parameter Group Parameter Name Access*
Min.
Range Default Setting
Max.
Range
Parameter
Units Installation Setting
Modbus
Register
(dec)