Constant Volume ECM Control, Cont’d.
1. Constant Dehumidication Mode: When the
dehumidication mode is selected (via DIP switch or
jumper setting), the ECM motor will operate with a
multiplier applied to the cooling CFM settings (approx.
20-25% lower airow). Any time the unit is running in
the cooling mode, it will operate at the lower airow
to improve latent capacity. The “DEHUM” LED will be
illuminated at all times. Heating airow is not affected.
Note: Do not select dehumidication mode if cooling
setting is tap 1.
2. Automatic (Humidistat-controlled): Dehumidication
Mode: When the dehumidication mode is selected (via
DIP switch) AND a humidistat is connected to terminal
DH, the cooling airow will only be reduced when the
humidistat senses that additional dehumidication is
required. The DH terminal is reverse logic. Therefore, a
humidistat (not dehumidistat) is required. The “DEHUM”
LED will be illuminated only when the humidistat is calling
for dehumidication mode. Heating airow is not affected.