CAUTION! 
For proper function of Shared Binary and Analog Inputs and Outputs, only one source of Shared 
Binary or Analog Outputs must be configured (i.e. it is not possible to configure in one controller 
SHBOUT1 and to another one as well SHBOUT1). 
SHBIN (1)
SHBOUT (2)
Not Received
Module SHBIN (2) is not 
inserted
SHBOUT (3)SHBIN (3)
CAN
Controller 2
Controller 3
Not Transimitted
Module SHBOUT (1) is not 
inserted
Level 1, Level 2 or no protection is displayed
 
7.16  Distributed Binary Inputs and Outputs 
InteliMains uses the same type of Distributed Binary Inputs and Outputs (DISTBIN and DISTBOUT 
modules) as InteliGen and InteliSys. Thanks to this, it is possible to share Binary and Analog values 
between all the controllers via CAN bus, thus saving physical Inputs and Outputs and excess wiring. 
DISTBIN and DISTBOUT work in a different way than SHBIN and SHBOUT. Each controller has one 
pack of eight DISTBOUT available (if not configured or no function is assigned to any output, it does 
not broadcast them). The number of DISTBOUT module is not shown in the configuration and it is 
always corresponding to the CAN address of the controller (e.g. the controller with address 5 will be 
broadcasting  DISTBOUT-05  which can  be received if  module DISTBIN-05 is  configured  in  another 
controller. Up to 32 DISTBIN modules can be configured (meaning that the controller will be receiving 
all DISTBOUT from all the controller, even his own). 
It is not possible to change the name of DISTBIN inputs or add protections. 
In the example below you can see 4 controllers with various DISTBIN and DISTBOUT configuration. 
DISTBOUT
DISTBIN
-01
DISTBIN
-02
DISTBIN
-03
DISTBIN
-04
Controller CAN 1
DISTBOUT
DISTBIN
-01
DISTBIN
-02
DISTBIN
-03
DISTBIN
-04
Controller CAN 2
DISTBOUT
DISTBIN
-01
DISTBIN
-02
DISTBIN
-03
DISTBIN
-04
Controller CAN 3
DISTBOUT
DISTBIN
-01
DISTBIN
-02
DISTBIN
-03
DISTBIN
-04
Controller CAN 4
CAN communication
 
NOTE:    
If SHUTDOWN (RED) protection is chosen, it is interpreted in InteliMains as Mains Protect with Reset 
type  protection.  For  more  information  on  Protection  types  and  alarms  please  refet  to  the  chapter 
Protection and Alarms management.