4.3  Programming of a controller 
4.3.1  Standard programming 
For programming GenConfig is used. Select correct connection mode and then select the following 
option: 
 
You  may  use  “FW  upgrade  (from  default configuration)”  (this  will  overwrite  all  of  the  settings  in  the 
controller with default settings. If you need to upgrade firmware from existing configuration, select “FW 
upgrade (from existing configuration)”. This function will automatically open wizard which will help you 
update the existing configuration to be compatible with the newly selected firmware. 
4.3.2  Programming of non-responsive controller 
If the controller does not contain valid firmware, new firmware cannot be programmed in the standard 
way. This situation can occur if the connection between the PC and the controller was interrupted e.g. 
during  a  previous  firmware  upgrade.  In  such  case  the  controller  may  have  a  blank  display  or 
connection to InteliVision may not be established and it does not communicate with the PC. The boot-
jumper must be used to get valid firmware into the controller. 
  Connect proper cable for programming (use RS232 port). 
  Open GenConfig and select “FW upgrade (default configuration)” 
  From the following table select FW that is required or click open and browse your files to find 
firmware in non-default location