InteliMains
NT
, SW version 3.0  
InteliMains-NT-BTB-3.0-Reference Guide.pdf, ©ComAp – June 2013   
Shared (virtual) Analog Input module 
Shared (virtual) Analog OUTput 
module 
Programmable (internal) logic module. 
 
NOTE: 
Maximum number of configured modules (both extension and virtual) is given by available addresses. 
The numbers in the table are valid in the case that no other modules are configured. 
16.2  Table of Analog Input functions 
16.2.1.1  Analog input: MLC:I/E-PbL 
This functional input is used for connecting of an external device, which 
measures the active power transferred from the busL to the busR. The 
device is connected to the controller via an analog input (e.g. -20 .. 20mA). 
The setpoint I/E-PbL meas must be set to the ANALOG INPUT position for 
this case. 
 
16.2.1.2  Analog input: MPF:I/E-QbL 
This functional input is used for connecting of an external device, which 
measures the reactive power transferred from the busL to the busR. The 
device is connected to the controller via an analog input (e.g. -20 .. 20mA). 
The setpoint I/E-QbL meas must be set to the ANALOG INPUT position for 
this case. 
 
16.2.1.3  Analog input: LCD brightness 
This functional input is used to adjust the backlight intensity of the IG-NT 
built-in terminal (display) by an analog input (e.g. a potentiometer). If this 
input is configured to a physical analog input or other value, the brightness 
adjusted by buttons at the terminal is overriden by this analog input. 
 
16.2.1.4  Analog input: Cold temp 1