Pn is the nominal power of the gen-set which is next to be stopped, the upper sum is the sum 
of the rest of the gen-sets running in power management. The lower sum is the sum of all the 
gen-sets currently running in power management.  
#%LdResStop is used from the currently selected reserve set. 
in BTB application many load control and power management functions does 
not play active role! 
This data object is intended for remote control of the gen-set via the 
communication if some kind of data is to be passed into the controller. 
This object can be written via the communication (e.g. Modbus) without any 
limitation. Use GenConfig function Generate Cfg Image to get the 
communication object number or register number of this particular value 
object. Below is a typical example of using this object. 
EXAMPLE:  
The gen-set group is required to be running in parallel-to-mains mode at 
constant load level (baseload), however the system baseload level is 
adjusted from a supervisory PLC system via Modbus. 
CAUTION!  
It is not allowed to solve this task by cyclic writing of the baseload setpoint 
from the supervisory device. The EEPROM memory may become damaged 
when any setpoint is written repeatedly with a short period.  
 
The proper solution is following: