InteliMains
NT
, SW version 3.0
InteliMains-NT-BTB-3.0-Reference Guide.pdf, ©ComAp June 2013
226
corresponding address is not available (does not exist of function on the CAN
bus) value "#####" is diplayed.
13.1.3.32 Value: Gen-set32 pwr
Group
Gen-sets
Units
kW
Related FW
3.0
Description
This value shows the actual power of corresponding genset (i.e. power of
genset with CAN address 1 is shown in Gen-set1 pwr). If genset with
corresponding address is not available (does not exist of function on the CAN
bus) value "#####" is diplayed.
13.1.4 Group: Control loops
13.1.4.1 Value: LSO
Group
Control loops
Units
%
Related FW
3.0
Description
Control loop for active power in percentage.
13.1.4.2 Value: VSO
Group
Control loops
Units
%
Related FW
3.0
Description
Control loop for reactive power in percentage.
13.1.5 Group: Power management
13.1.5.1 Value: TotAvlbPnom
Group
Pwr management