7.19  Analog Input Sensors and User Sensors 
Controller and/or some extension modules allow connection of sensor outputs to Analog Inputs. There 
is  whole  variety  of  common  sensor  output  characteristics  prepared  in  configuration  by  default. 
Although if there is sensor that is not in the list, it is possible to prepare custom characteristics (up to 
16) with up to 31 definition points. 
Name of the 
Analog Input
Dimension
Connected Sensor
(default and user 
sensors)
Resolution and Range of the sensor (in 
some cases this is fixed by sensor type 
and cannot be changed)
Interpretation of 
the received value 
in bar graph form
Offset of the 
received value
 
Figure: Sensor adjustment in GenConfig 
Default sensors: PT100/°C, PT1000/°C, NI1000/°C, PT100/°F, PT1000/°F, NI1000/°F,   
     4-20mA active, 0-2400ohm, 0-2.4V, Tristate 
HINT 
There is “electronic” type of sensor available for Shared Analog Inputs which can be used to interpret 
shared data over CAN bus.