InteliMains
NT
, SW version 3.0  
InteliMains-NT-BTB-3.0-Reference Guide.pdf, ©ComAp – June 2013   
9.1.3  Following graphs depict possible CB sequences: 
Repeated CB close command (second succesfull – left, second unsuccesfull – right): 
 
0
1
0
1
0
1
0
1
0
1
0
1
CB UV coil
CB ON coil
CB OFF coil
CB fdb
CB fdb neg
CB close
/
open
0
1
CB status
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
CB fail
1s
2s
2s
1s
2s
1s
2s
2s
1s
2s
BO/BI
CB status switches after both 
feedbacks (fdb and fdb neg) are in 
correct position. 
Minimum 1s delay after UV coil is 
switched on is needed before CB can 
be closed 
0
1
0
1
0
1
0
1
0
1
0
1
1s
2s
BO/BI
CB close
/
open
CB UV coil
CB ON coil
CB fdb
CB fdb neg
If the CB is not closed after 
the first attempt, it is only 
reset by OFF pulse and no 
CB fail is issued. This would 
be issued after the second 
unsuccessfull attempt. 
ON pulse has finished and 
CB status is not =1. CB fail 
is issued immediatelly