controller even in the case of power supply failure. Physical unit of the output 
statistic value has to correspond to the ratio unit “/X”.  
NOTE:  
Pulse width (both high/low levels) must be at least 100 ms in order to be 
correctly sensed! Conversion ratio can be selected using the setpoints 
ConvCoefPulse1/2/3/4. The converted values are visible in statistics – values 
PulseCounter 1/2/3/4. These values can be reset using Statistics window in 
InteliMonitor.  
 
 
 
12.2.3  Group: Comms settings  
12.2.3.1  Setpoint: Controller name 
This setpoint is intended for a custom name of the controller, which is used 
for identification of the controller in saved archives or remote connections. 
Maximal length of the name is 15 characters. 
The setpoint can't be modified via the IG-NT built-in terminal. 
 
12.2.3.2  Setpoint: LB/UART Log 
The setpoint enables/disables logging of remote communication activity. If 
logging is enabled connection and disconnection of each remote terminal as 
well as entering access code are recorded into the history. 
NOTE:  
The terminal is disconnected automatically after 5 min of inactivity and next 
communication request from the same terminal is considered as a new 
connection. When logging is enabled in certain conditions the history may be 
filled up with large number of records related to the communication and 
important records may be overwritten quite fast.