InteliMains
NT
, SW version 3.0  
InteliMains-NT-BTB-3.0-Reference Guide.pdf, ©ComAp – June 2013   
Ld shed delay
Ld shed delay
Ld shed delay
BO LdShed stage 1
BO LdShed stage 2
BO LdShed stage 3
Ld shed level
Mains import or 
gen-sets power
Time
 
Ld recon delay
Ld recon delay
Ld recon delay
BO LdShed stage 1
BO LdShed stage 2
BO LdShed stage 3
Ld recon level
Time
Mains import or 
gen-sets power
 
Ld recon delay
Ld recon delay
Ld recon delay
BO LdShed stage 1
BO LdShed stage 2
BO LdShed stage 3
Ld recon level
Mains import or 
gen-sets power
Time
BI ManualLdRecon
 
 
Figure: Examples of load shedding and load reconnection (load shed, load recon, manual load recon) 
7.5  Remote Alarm Messaging 
It is possible to use up to five channels for Active Call, Email and SMS upon defined type of Alarm. It 
is  possible  to  define  protection  type  for  all  ENABLED  channels  to  react.  All  the  possibilities  in 
InteliMains are: History record, Alarm only, Warning, Breaker open and BrkOpen w/Reset. Find more 
information about alarm types in the chapter Protections and alarm management. 
7.5.1  Communication Types for Remote Alarm Messaging 
Below there all types of communication available for each Active Call channel. 
DATA-ANA: This option sends a complete archive to the recipient's PC via analog modem. An analog 
modem must be connected either to one of controller COM ports or to one of I-LB modules connected 
to the controller via CAN2 bus. The channel address must contain complete telephone number of the 
recipient's PC where InteliMonitor is running in Active call receiving mode.