InteliMains
NT
, SW version 3.0  
InteliMains-NT-BTB-3.0-Reference Guide.pdf, ©ComAp – June 2013   
This setpoint determines the delay which is used in evaluation of BusR V 
unbal protection (threshold for this protection is set by the setpoint BusR V 
unbal).  
 
12.2.8  Group: Pwr management 
12.2.8.1  Setpoint: #Pwr mgmt mode 
ABS(kW), ABS(kVA), REL (%) [-] 
The power management is based on actual sum of active 
power of gen-sets participating in the power management 
in particular control group (TotRunPact) and sum of active 
nominal power of gen-sets participating in the power 
management in particular control group (TotRunPnom). 
Setpoints #LoadResStrt X (e.g. LoadResStrt 1) and 
#LoadResStop X (e.g. LoadResStop 1) are set in absolute 
values in kW.  
The power management is based on actual sum of 
apparent power of gen-sets participating in the power 
management in particular control group (given by 
TotRunPact and total reactive power, S^2 = P^2 + Q^2) 
and sum of apparent nominal power of gen-sets 
participating in the power management in particular control 
group (this value is given for each gen-set as Nomin 
current multiplied by GenNomV). Setpoints #LoadResStrt 
X (e.g. LoadResStrt 1) and #LoadResStop X (e.g. 
LoadResStop 1) are set in absolute values in kVA.  
The power management is based on the relative load, i.e. 
ratio active power to nominal power. Setpoints 
#%LdResStrt X (e.g. %LdResStrt 1) and #%LdResStop X 
(e.g. %LdResStop 1) are set in relative values in %. 
Minimum allowable relative power reserve is evaluated 
from nominal power of all running gen-sets combined in %.  
 
NOTE:  
# sign in the name of this setpoint marks that this setpoint is shared among 
all controllers connected by CAN2 bus.