InteliMains
NT
, SW version 3.0
InteliMains-NT-BTB-3.0-Reference Guide.pdf, ©ComAp June 2013
156
It is not destined for normal operation. Please refer to the Troubleshooting
guide for more information (chapter "MGCB is not closed although gensets
are running").
NOTE:
# sign in the name of this setpoint marks that this setpoint is shared among
all controllers connected by CAN2 bus.
12.2.8.7 Setpoint: #LoadResStop 1
Group
Pwr Management
Range [units]
LoadResStrt 1 .. 32000 [kX]
Related FW
3.0
Description
This setpoint is used to adjust the load reserve for stop in absolute mode. i.e.
Pwr mgmt mode = ABS (kW) or ABS (kVA) if the reserve set #1 is active.
Learn more about reserves in the chapter Reserves, minimal running power.
The currently active reserve set is selected by binary inputs Load res 2, Load
res 3 and Load res 4. If none of these inputs is active the set #1 is selected.
NOTE:
The reserve for stop must be always adjusted higher than the reserve for
start.
NOTE:
# sign in the name of this setpoint marks that this setpoint is shared among
all controllers connected by CAN2 bus.
12.2.8.8 Setpoint: #LoadResStrt 2
Group
Pwr Management
Range [units]
-32000 .. LoadResStop 2 [kX]
Related FW
3.0
Description
This setpoint is used to adjust the load reserve for start in absolute mode. i.e.
Pwr mgmt mode = ABS (kW) or ABS (kVA) if the reserve set #2 is active.
Learn more about reserves in the chapter Reserves, minimal running power.
The currently active reserve set is selected by binary inputs Load res 2, Load
res 3 and Load res 4. If none of these inputs is active the set #1 is selected.
NOTE: