InteliMains
NT
, SW version 3.0  
InteliMains-NT-BTB-3.0-Reference Guide.pdf, ©ComAp – June 2013   
When the BO CB close/open opens, there is 5 resp. 2 sec delay for the breaker to respond before a 
CB fail is detected. In such case, if CB OFF coil is used for opening the CB and CB fail occurs during 
opening the CB, the signal CB OFF coil is automatically extended until the breaker opening is 
detected (evaluated as CB status). 
  2 sec when the CB is used for synchronizing 
  5 sec in other cases 
 
0
1
0
1
0
1
BO/BI
CB fdb
CB fail
CB close
/open
0
1
0
1
0
1
2s5s
 
  In case that CB fail is detected after switching the controller on (CB is closed), the CB OFF coil 
output is activated immediatelly. 
  Important: 
In  case  that  BTB  feedback  is  active  (BTB  is  expected  to  be  closed)  and  “BTB  fail”  is 
reported due to previous incorrect manipulation of BTB, in the moment of Fault reset, the 
BTB fail is cleared and the controller internally goes to “closed” state. I.e. BTB fdb status is 
confirmed and the output BTB close/open is energized. 
9.1.4  Follow function for breaker control in AUT mode 
Only in MCB application. 
Using setpoint ProcessControl:BrkCtrl in AUT behavior of breaker control can be adjusted. 
PROCESSCONTROL:BRKCTRL IN 
AUT 
Breaker is controller by the controller. 
Breaker  is  controlled  externally  and  the  controller  does  not 
attempt to control it nor any alarms are issued. Synchronization 
process can be started by the FORCE SYNC input if it is allowed by 
the setpoints ProcessControl:Synchro enable.  Synchronization 
in  COX(FOLLOW)  does  not  have  any  timeout  and  controller 
keeps voltages synchronized indefinitely (i.e. until FORCE SYNC is 
opened or the breaker is closed externally).