InteliMains
NT
, SW version 3.0  
InteliMains-NT-BTB-3.0-Reference Guide.pdf, ©ComAp – June 2013   
Shared (virtual) Analog Input module 
Shared (virtual) Analog OUTput 
module 
Programmable (internal) logic module. 
 
NOTE: 
Maximum number of configured modules (both extension and virtual) is given by available addresses. 
The numbers in the table are valid in the case that no other modules are configured. 
15.2  Table of Binary Output functions 
15.2.1.1  Binary output: BTB Close/Open 
This output is intended for control of the BTB if a contactor is used as BTB. The output 
provides continuous signal while the BTB has to be closed. See timing diagram of all 
available breaker control outputs at the bottom of this description. 
NOTE:  
Use invert function when configuring the output in GenConfig to obtain inverted function 
of the output, i.e. output is closed while the BTB has to be open.  
 
There are also other outputs availabe for BTB control:  
  BTB ON coil 
  BTB OFF coil 
  BTB UV coil