Bus Right Voltage Unbalance 
BusL protect: BusR V unbal; BusR V unb del 
Analog protect: Batt >V; Batt <V; Batt volt del 
8.1.4  Bus left voltage and frequency protections - limits and 
indications 
IDMT  Current:  This  protection  can  be  activated  or  deactivated  by  the  setpoint 
BusL Protect:BusL2Inom prot.  For more information on  the  dynamic  delay of  this protection 
refer  to  the setpoint  BusL Protect:BusL2Inom  del  in  the  APPENDIX  of  this  document  or  in 
context help in GenConfig. 
IDMT  Active  Power:  This  protection  can  be  activated  or  deactivated  by  the  setpoint 
BusL Protect:BusL2POvrldPro. BusL protect:OveldStrtEval setpoint defines when the IDMT 
Active Power protection starts to be evaluated. For more information on the dynamic delay of 
this protection refer to the setpoint BusL Protect:2POVrldStrtEvDel in the APPENDIX of this 
document or in context help in GenConfig. 
BusL Over and Under Voltage: This protection limits are given by setpoints BusL protect:BusLeft 
>V,  BusL protect:  BusLeft  <V.  Delay  for  over  and  under  voltage  is  given  by  the  setpoint 
BusL protect:BusLeft V del. Protection is indicated by message “BL LX over” (X = number of 
corresponding  phase)  or  “BL  LX  under”.  When  Basic  settings:FixVoltProtSel  is  adjusted  to 
PHASE-PHASE then this protection is evaluated based on voltage between phases and it is 
indicated by “BL LXY over” or “BL LXY under” (where XY are number of corresponding phases). 
BusL  Over  and  Under  Frequency:  This  protection  limits  are  given  by  setpoints 
BusL protect:BusLeft  >f,  BusL protect:  BusLeft  <f.  Delay  for  over  and  under  frequency  is 
given by the setpoint BusL protect:BusLeft f del.  Protection  is  indicated  by message “BusL  f 
over” or “BusL f under”. 
8.1.5  Bus right voltage and frequency protections - limits and 
indications 
BusR Over and Under Voltage: This protection limits are given by setpoints BusR protect:BusRight 
>V,  BusR protect:  BusRight  <V.  Delay for  over  and  under  voltage  is  given  by  the  setpoint 
BusR protect:BusRight V del. Protection is indicated by message “BR LX over” (X = number of 
corresponding  phase)  or  “BR  LX  under”.  When  Basic  settings:FixVoltProtSel  is  adjusted  to 
PHASE-PHASE then this protection is evaluated based on voltage between phases and it is 
indicated  by  “BR LXY  over”  or  “BR  LXY  under”  (where  XY  are  number  of  corresponding 
phases). 
BusR  Over  and  Under  Frequency:  This  protection  limits  are  given  by  setpoints 
BusR protect:BusRight >f, BusR protect: BusRight <f. Delay for over and under frequency is 
given by the setpoint BusR protect:BusRight f del. Protection is indicated by message “BusR f 
over” or “BusR f under”. 
8.1.6  User configurable protections 
Controller provides vast possibilies for user configurable protections. There are several protections 
that configured by default in standard configuration. For step-by-setp guide on how to configure your 
own protections please go to chapter 7.1.6.2.