InteliMains
NT
, SW version 3.0  
InteliMains-NT-BTB-3.0-Reference Guide.pdf, ©ComAp – June 2013   
This is a bit array containing status of logical binary outputs 97-113 of the 
controller. Bit0 represents LBO97, bit1 represents LBO98 etc..  
NOTE:  
All terminals display binary values in "human-readable" form - from left to 
right. That means the bit 0 is displayed in the most left position. This is 
different from common use in computer science, where binary values are 
displayed from right to left.  
 
NOTE:  
Click on button with "..." to get a clear list of BI names with their 
corresponding values.  
 
 
13.1.11.8  Value: RemoteControls 
This is a bit array containing status of the binary outputs Remote control1 ... 
Remote control8.  
NOTE:  
Click on button with "..." to get a clear list of BI names with their 
corresponding values.  
 
 
13.1.12  Group: Info 
13.1.12.1  Value: Controller mode 
This value contains actual controller mode. The controller mode is selected 
by the setpoint Controller mode but the setpoint position can be overriden by 
binary inputs Remote OFF, Remote MAN, Remote AUT or Remote TEST.