InteliMains-NT-BTB-3.0-Reference Guide.pdf, ©ComAp – June 2013   
In the figure above the signal of logical function CtrlHBeat FD is used to disable the main controller if it 
is lost from CAN bus or CAN bus communication from that controller becomes erratic. It is used also 
to disable the redundant controller when the communication on CAN bus is alright (it is negated). For 
more  information  on  Virtual  Binary  Inputs  and  Outputs  (VPIO)  please  refer  to  the  chapter  about 
Shared Binary Inputs and Outputs and Virtual Binary Inputs and Outputs. 
NOTE:    
Use pulse signals for control of circuit breakers. LCB ON COIL and LCB OFF COIL should be used to 
prevent  sudden  opening  for  a  short  period  of  time  when  the  controller  fails  and  to  ensure  proper 
function of redundancy. 
7.7  Force value – step by step guide 
In this chapter there is complete step by step guide which shows how to use Force value function of 
the controller. 
Forcing of values is used to change particular setpoint temporarily by activation of related Binary Input. 
This  is  used  to  change  function  of  controller  under  given  conditions  (e.g.  there  are  two  different 
periods during the day when Export limit given by distribution network is required or not). 
WARNING!  
Setpoints must not be written continuously (e.g. via Modbus connection)! If continuous change of 
setpoints is required, combination of External values and Force value function needs to be used. The 
memory that holds setpoints is designed for up to 10
5
 writings. Than memory may be damaged! 
Setpoints that are available for forcing may be identified by Force value button on the right side in 
GenConfig (see the figure below). 
 
When the button is clicked, Force value dialog appears. 
Add or remove Force value
Change position of Force value functions (priority)
Change the name of the source setpoint
(available only for Force value 1-16 setpoints)
Select the value that should be forced (i.e. 
the value of the particular setpoint)
Rename binary input that 
triggers the forcing
ID of binary input
(1 for ForceValueIn 1 etc.)
Select source setpoint or value