DATA-GSM: This option sends a complete archive to the recipient's PC via GSM modem. A GSM 
modem with activated CSD data transfers must be connected either to one of controller COM ports or 
to one of I-LB modules connected to the controller via CAN2 bus. The channel address must contain 
complete telephone number of the recipient's PC where InteliMonitor is running in Active call receiving 
mode.   
DATA-ISDN: This option sends a complete archive to the recipient's PC via ISDN modem. An ISDN 
modem must be connected either to one of controller COM ports or to one of I-LB modules connected 
to the controller via CAN2 bus. The channel address must contain complete telephone number of the 
recipient's PC where InteliMonitor is running in Active call receiving mode.   
DATA-CDMA: This option sends a complete archive to the recipient's PC via CDMA modem. A CDMA 
modem must be connected either to one of controller COM ports or to one of I-LB modules connected 
to the controller via CAN2 bus. The local CDMA network must allow point-to-point data transfers. The 
channel address must contain complete telephone number of the recipient's PC where InteliMonitor is 
running in Active call receiving mode.   
SMS-GSM: This option sends a short text message (SMS) containing the actual Alarmlist contents to 
the  recipient's  mobile  phone  via  the  GSM  modem.  The  channel  address  must  contain  complete 
telephone number of the recipient's mobile phone.  
SMS-CDMA: This option sends a short text message (SMS) containing the actual Alarmlist contents 
to the recipient's mobile phone via the CDMA modem. The channel address must contain complete 
telephone number of the recipient's mobile phone.   
IB-E-MAIL: This option sends an e-mail containing the actual Alarmlist contents and latest 20 history 
records (only date, time, reason) to the recipient's mailbox via the IB-COM module or IG-IB module. 
The channel address must contain valid e-mail address of the recipient.  
NOTE:    
The  SMTP  settings  (SMTP  authent,SMTP  user  name,  SMTP  password,  SMTP  address,  Contr 
mailbox) must be properly adjusted for sending e-mails.   
7.5.2  Example of setting 
There is an example of setting of Remote Alarm Messaging. In this case active calls we be triggered 
on  Breaker open  and  BrkOpen w/Reset  alarms.  Message  is  sent  via  email  to 
emailAddress@domain.com  (Channel  1  –  available  for  NTC  controller  or  with  any  controller  with 
connected IB-NT or I-LB+), archive is sent via ISDN modem to the number +111222333444 (Channel 
2) and SMS is sent to the number +999111333555 (Channel 3). 
 
It is also possible to adjust number of attempts that controller performs in case of not successful Active 
Call  –  Comms settings:ActCallAttempt.  The  language  of  messages  can  be  changed  – 
Comms settings:Acall+SMS  lang  (use  Translator  and  Languages  tabs  in  GenConfig  to  adjust 