InteliMains
NT
, SW version 3.0  
InteliMains-NT-BTB-3.0-Reference Guide.pdf, ©ComAp – June 2013   
1.  Go to GenConfig, download the configuration from the controller, 
select the LAI tab and configure the logical analog input 
MLC:AnExSysBld onto the ExtValue1, which is located in the Force 
value group. If you do not see the LAI tab you have to switch the 
GenConfig to "advanced" mode. Then upload the configuration into 
the controller.  
2.  Go to InteliMonitor and change the setpoint MLoad ctrl PtM to 
ANEXSYSBLD->LS.  
3.  Now you have to program your PLC to write requested gen-set 
baseload into the Modbus register ExtValue1 (register number 40392 
for IG/IS-NT-2.4).  
 
 
13.1.6.2  Value: ExtValue2 
This data object is intended for remote control of the IntelliMains via the 
communication if some kind of data is to be passed into the controller. 
This object can be written via the communication (e.g. Modbus) without any 
limitation. Use GenConfig function Generate Cfg Image to get the 
communication object number or register number of this particular value 
object. See an example at the object ExtValue1. 
 
13.1.6.3  Value: ExtValue3 
This data object is intended for remote control of the IntelliMains via the 
communication if some kind of data is to be passed into the controller. 
This object can be written via the communication (e.g. Modbus) without any 
limitation. Use GenConfig function Generate Cfg Image to get the 
communication object number or register number of this particular value 
object. See an example at the object ExtValue1. 
 
13.1.6.4  Value: ExtValue4