Setpoint group Engine parameters Related FW 2.5.0
Range [units] 0 .. 1000 [min]
Default value 0 -
Step 1
Comm object 11837 Related applications
Description
Automatic engine stop in MAN mode or delayed engine stop in AUT mode. Start engine in MAN mode by
START button. Engine stops itself after Running Timer is over. Engine stays running when Running timer
(page 125) = 0
Running timer
6 back to List of setpoints
Setpoint group Engine parameters Related FW 2.5.0
Range [units] 0 .. 10000 [L]
Default value 200 -
Step 1
Comm object 11103 Related applications
Description
This setpoint is describing volume of fuel tank for counting fuel consumption depending on Fuel level drop.
FuelTankVolume
6 back to List of setpoints
Setpoint group Engine parameters Related FW 2.5.0
Range [units] 0 .. 50 [%/h]
Default value 25 -
Step 1
Comm object 12373 Related applications
Description
This is setting protection against the fuel leakage or theft.
Function monitors the AIN3 Fuel level value in percentage scale without decimals. The alarm and history
record “Wrn FuelTheft” is activated when Fuel level change is faster than setpoint limit. Function is switched
off when Max Fuel Drop = 0 %/h.
The drop out limit on stopped engine is 5% to avoid unwanted Alarm activation due to AIN3: Fuel level
fluctuations.
Active alarm "Wrn FuelTheft" can be sent via SMS and displayed by WebSupervisor (if used).
Note: Set 0 to disable Fuel Theft Protection function into MaxFuelDrop setpoint.
MaxFuelDrop
6 back to List of setpoints